Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 12/14/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) BLAKE TEE IS LISTED FOR VERTICAL USE IN WALL 2) SEC 312.2 IPC REQUIRES THAT WHEN TEST IN SECTION, THE UPPER MOST 10' OF THE PREVIOUSLY TESTED SECTION SHALL BE RE-TESTER SO THAT NO JOINT GOES WITHOUT AT TEST |
|
| 12/12/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE WYE PATTERN TEST FITTINGS, INSTALLED IN THE PROPER DIRECTION OF FLOW 2) INSTALL ABOVE SLAB TEST FITTINGS SO THAT NO JOINTS ABOVE SLAB GO WITHOUT A TEST 3) REMOVE ROCKS & DEBRIS, SHADE PIPING WITH CLEAN FILL |