Permit: T11CM03028

Parcel: 12108093A


Addresses:

6280 E PIMA ST #110


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM03028

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/14/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) BLAKE TEE IS LISTED FOR VERTICAL USE IN WALL
2) SEC 312.2 IPC REQUIRES THAT WHEN TEST IN SECTION, THE UPPER MOST 10' OF THE PREVIOUSLY TESTED SECTION SHALL BE RE-TESTER SO THAT NO JOINT GOES WITHOUT AT TEST
12/12/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE WYE PATTERN TEST FITTINGS, INSTALLED IN THE PROPER DIRECTION OF FLOW
2) INSTALL ABOVE SLAB TEST FITTINGS SO THAT NO JOINTS ABOVE SLAB GO WITHOUT A TEST
3) REMOVE ROCKS & DEBRIS, SHADE PIPING WITH CLEAN FILL