Permit: T11CM02993

Parcel: 10510062G

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T11CM02993

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2011 PLUMBING - FINAL Approved BACTERIA & STERILIZATION REPORTS OK. INSPECTIONS NOTED BY RMYERS ON 11/15 ARE FOR DIFFERENT SITE.
11/15/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
11/15/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BAR WAS ONE SIDED WITHOUT RAIL GUARDS
2) INSULATION NOT INSTALLED PER MANUFCATURES SPECS, NO LAGGING ADHESIVE, NO TAPE AND NOT CONTINOUS
3) SINK DRAIN FLOOR SINK MAY NOT SPLASH OR FLOOD
4) PROVIDE VENTED ACCESS PANEL FOR AABS
5) STILL NO METHOD OF STERILIZATION AND STILL NO CLEAN BACTERIA REPORT
6) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE
11/14/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLAN, PERMIT AND COMPLETE INSPECTION HISTORY TO BE ON SITE AT ALL TIMES
2) UNABLE TO LOCATE LETTER ALLOWING PEX
3) UABLE TO LOCATE METHOD OF STERILIZATION OR CLEAN BACTERIA REPORT
11/09/2011 PLUMBING - FINAL Not ready for Inspection 1) METHOD OF STERILIZATION
2) CLEAN BACTERIA REPORT
3) MIXING VALVES MAY NOT BE SUPPORTED BY THE TUBING