Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM02993
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2011 | PLUMBING - FINAL | Approved | BACTERIA & STERILIZATION REPORTS OK. INSPECTIONS NOTED BY RMYERS ON 11/15 ARE FOR DIFFERENT SITE. | |
11/15/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/15/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BAR WAS ONE SIDED WITHOUT RAIL GUARDS 2) INSULATION NOT INSTALLED PER MANUFCATURES SPECS, NO LAGGING ADHESIVE, NO TAPE AND NOT CONTINOUS 3) SINK DRAIN FLOOR SINK MAY NOT SPLASH OR FLOOD 4) PROVIDE VENTED ACCESS PANEL FOR AABS 5) STILL NO METHOD OF STERILIZATION AND STILL NO CLEAN BACTERIA REPORT 6) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE |
|
11/14/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLAN, PERMIT AND COMPLETE INSPECTION HISTORY TO BE ON SITE AT ALL TIMES 2) UNABLE TO LOCATE LETTER ALLOWING PEX 3) UABLE TO LOCATE METHOD OF STERILIZATION OR CLEAN BACTERIA REPORT |
|
11/09/2011 | PLUMBING - FINAL | Not ready for Inspection | 1) METHOD OF STERILIZATION 2) CLEAN BACTERIA REPORT 3) MIXING VALVES MAY NOT BE SUPPORTED BY THE TUBING |