11/21/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
11/17/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT #6 AND CONDUIT TO WALL 2) SIGN ON DISC. SW. IN CARPORT EPR 690.17 NEC 3) RELOCATE LADDER TO WEST SIDE AT HIGH POINT OF ROOF FOR BETTER VIEW OF UNDER PV PANEL. NEED TO VERIFY GROUNDING OF PANELS (TILE ROOF) |
|