Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2012 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2012 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ONLY ONE SLIP NUT ALLOWED ON THE OUTLET SIDE OF THE TRAP 2) FINISH INSULATION AT WATER HEATER 3) SUPPORT RECIRC. PUMP 4) REQUIRE 15" FROM CENTER LINE TO SIDE WALL OR OBSTRUCTION ON WATER CLOSET. 18" CENTER TO SIDEWALL OR OBSTRUCTION FOR HANDI CAPPED 5) REMOVE COVERS ON EWC 6) CLEANOUT EXTERIOR FLOOR SINKS AND INSTALL STRAINERS 7) URINAL TO BE 17" AFF TO OVERFLOW MAX 8) METHOD OF STERILIZATION 9) CLEAN BACTERIA REPORT AND BACKFLOW CERT |