Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM02963

Parcel: 12709011K


Addresses:

6129 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11CM02963

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2012 FIRE SPKLR - FINAL Approved
03/14/2012 FIRE SPKLR - FINAL Denied 1. Head in existing outside corridor needs to be replaced due to being painted.

2. Sprinkler head in freezer needs to be adjusted for coverage. Coverage needs to be 7 1/2 ft. or less from wall.