Permit: T11CM02954

Parcel: 13705495A


Addresses:

1150 W DREXEL RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T11CM02954

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2011 FIRE - ALARM FINAL Approved
12/01/2011 FIRE - ALARM FINAL Partial Approval 1. Repair or replace smoke duct detectors to give a clear green light on the fire alarm control panel.
2. Add lock outs on all breakers to main fire alarm panel and nac's.
3. Cover hole in Fire alarm control panel room x1