Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11CM02954
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2011 | FIRE SPKLR - FINAL | Approved | ||
12/01/2011 | FIRE SPKLR - FINAL | Partial Approval | Correct sprinkler coverage in storage room by bathrooms 129 & 130 | |
10/11/2011 | FIRE SPKLR - FINAL | Denied | 1. Correct sprinkler coverage northeast by entrance door, head over 9 feet of wall, 2. Top of stairs painted head - replace. 3. No storage allowed in riser room. 4. Replace all missing ceiling tiles and repair any holes in ceiling. 5. Need finals for FM200 system and pre-action system. |