Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM02954
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/13/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST AXC-3 OK, AC-7 OK, AC-8 OK, AC-4 OK AC-5 OK AC-9 OK, AC10 AND AC-6 NOT WORKING AT THIS TIME, OPEN AREA 170 WEST HALF NO OTHER LIFE SAFETY ISSUES OBSERVED, SEE BLDG INSPECTOR FOR TEMP C OF O |
|
10/12/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/07/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/05/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/04/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DUCT ABOVE RESTROOMS 151 AND 152 OK TO COVER, NORTH WALL OF OPEN AREA 170, DUCT THROUGH WALL OK TO COVER |