Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM02936
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
09/30/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABELS FROM TEP AND NEC ON SERVICE MISSING 2) LB IN GARAGE HAS CONNECTOR MISSING 3) CHECK GROUNDING ELECTRODE BONDING IN DISCONNECT AND DC LANDED ON GROUNDING LUG NOT ELECTRODE LUG ON INVERTER |
|
09/28/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |