Permit: T11CM02898

Parcel: 12510003F


Addresses:

3435 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02898

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/24/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/24/2013 MECHANICAL - FINAL Partial Approval SMOKE TEST ON GREASE DUCTS OK
STILL NEED AIR BALANCE, CAPTURE, & CONTAINMENT, & HEAT SENSOR TESTS.
EXTEND ELEC CONDUIT TO EX FANS
07/23/2013 MECHANICAL - FINAL Not ready for Inspection PROVIDE A SMOKE TEST ON GREASE DUCT. SECURE ELECTRICAL CONNECTIONS, CHECK WHIP LENGTH. GREASE EXHAUST HOOD SHALL NOT REQUIRE THE USE OF TOOLS TO SERVICE. DO NOT SCREW IT SHUT. HASP OK. TOILET RM FANS SHALL RUN CONTINUOUS PER M3 FAN SCH. PROVIDE SLOPE ON WH VENT. CORRECT SIZING OF HYBRID UNIT DRAIN. MAY NOT REMOVE. ALSO UV PROTECTION. REPLACE BROKEN ZIP TIE SUPPORTS BETWEEN REFER CASES. PROVIDE TEST & BAL REPORTS.
07/22/2013 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
07/22/2013 MECHANICAL - FINAL Not ready for Inspection - MISSING FIXTURES. RO EQUIPMENT NOT YET INSTALLED
- PROVIDE NON-POTABLE LABELS & HYBRID HOSE BIBS
- PROVIDE ALL DOCUMENTATION
- GAS CONN MISSING AT OVEN