Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM02898
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2013 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
07/24/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
07/24/2013 | MECHANICAL - FINAL | Partial Approval | SMOKE TEST ON GREASE DUCTS OK STILL NEED AIR BALANCE, CAPTURE, & CONTAINMENT, & HEAT SENSOR TESTS. EXTEND ELEC CONDUIT TO EX FANS |
|
07/23/2013 | MECHANICAL - FINAL | Not ready for Inspection | PROVIDE A SMOKE TEST ON GREASE DUCT. SECURE ELECTRICAL CONNECTIONS, CHECK WHIP LENGTH. GREASE EXHAUST HOOD SHALL NOT REQUIRE THE USE OF TOOLS TO SERVICE. DO NOT SCREW IT SHUT. HASP OK. TOILET RM FANS SHALL RUN CONTINUOUS PER M3 FAN SCH. PROVIDE SLOPE ON WH VENT. CORRECT SIZING OF HYBRID UNIT DRAIN. MAY NOT REMOVE. ALSO UV PROTECTION. REPLACE BROKEN ZIP TIE SUPPORTS BETWEEN REFER CASES. PROVIDE TEST & BAL REPORTS. | |
07/22/2013 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/22/2013 | MECHANICAL - FINAL | Not ready for Inspection | - MISSING FIXTURES. RO EQUIPMENT NOT YET INSTALLED - PROVIDE NON-POTABLE LABELS & HYBRID HOSE BIBS - PROVIDE ALL DOCUMENTATION - GAS CONN MISSING AT OVEN |