Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/12/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CHASE NIPPLE ON LP AT METER CANNOT BE USED AS A BOND 2) GROUNDING ELECTRODE IN INVERTER LANDED ON WRONG LUG 3) TEP LABELS MISSING AND NEC LABEL MISSING ON INSTALL |