Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2012 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection :* | |
| 02/22/2012 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) OVERLAPS ON 2ND LAYER FIRE WRAP TO BE MINIMUM 3" BANDING TO BE WITHIN 1 1/2" OF EACH EDGE AND 10 1/2" SPACING 2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX |
|
| 02/17/2012 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* 1) WELD DUCT AT HOOD CONNECTION |