Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM02840
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/26/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH #3, 4 & 5 PREVIOUS INSPECTION 2) CHECK ON FINAL |
|
10/24/2011 | ELECTRIC - ABOVE CEILING | Cancelled | CANCELLED PER CONTRACTOR CHRIS BOWEN #401-3111 | |
10/24/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
10/21/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) DO NOT WRAP WIRE AROUND METAL SUPPORT AND SUPPORT PROPERLY 2) SECURELY ATTACH FIXTURES TO GRID-IF MANUFACTURERS CLIPS USED MUST BE EFFECTIVE 3) M/C SUPPORT WIRES 300.11 4) VDV TO BE 725.3 & 8, 800.2 & 24 AND 300.11 5) TY WRAPS NOT ALLOWED AIR HANDLING SPACE 6) NEED 2 SUPPORT WIRES FOR FIXTURES 2 X 4'S-1 PER 4 FOOT OF TRAC 2 FOR STRIP LIGHTS 7) TERMINATE GEC FOR SEPERATELY DIRIVED SYSTEM 8) BOXES OVER FILLED |