Permit: T11CM02840

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/16/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/26/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH #3, 4 & 5 PREVIOUS INSPECTION
2) CHECK ON FINAL
10/24/2011 ELECTRIC - ABOVE CEILING Cancelled CANCELLED PER CONTRACTOR CHRIS BOWEN #401-3111
10/24/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
10/21/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) DO NOT WRAP WIRE AROUND METAL SUPPORT AND SUPPORT PROPERLY
2) SECURELY ATTACH FIXTURES TO GRID-IF MANUFACTURERS CLIPS USED MUST BE EFFECTIVE
3) M/C SUPPORT WIRES 300.11
4) VDV TO BE 725.3 & 8, 800.2 & 24 AND 300.11
5) TY WRAPS NOT ALLOWED AIR HANDLING SPACE
6) NEED 2 SUPPORT WIRES FOR FIXTURES 2 X 4'S-1 PER 4 FOOT OF TRAC 2 FOR STRIP LIGHTS
7) TERMINATE GEC FOR SEPERATELY DIRIVED SYSTEM
8) BOXES OVER FILLED