Permit: T11CM02818

Parcel: 108214280

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM02818

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/07/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH FLOOR BOXES
10/06/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SECURE POWER PULE TO GRID
2) TIGHTEN LOOSE FITTINGS
3) USE LISTED/APPROVED FITTINGS WITH SBAC TILE
4) SECURE TOP OF POWER POLE
5) FINISH MODULAR FURNITURE 605.5 & 7
6) FINISH FLOOR BOXES
7) EXIT SIGN NOT WORKING
8) PANEL DIRECTERIES 408.4
09/29/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EM LIGHTING NOT WORKING
2) BOXES MORE THAN 1/4"314.20
3) REVISE PANEL DIRECTORIES 408.4
4) MODULAR FURNITURE TO BE PER 605.5 & 7
5) NEED TO SEE MODULAR FURNITURE CONNECTIONS
6) OK TO BRING FURNITURE ON SITE