Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM02818
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/07/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH FLOOR BOXES |
|
10/06/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE POWER PULE TO GRID 2) TIGHTEN LOOSE FITTINGS 3) USE LISTED/APPROVED FITTINGS WITH SBAC TILE 4) SECURE TOP OF POWER POLE 5) FINISH MODULAR FURNITURE 605.5 & 7 6) FINISH FLOOR BOXES 7) EXIT SIGN NOT WORKING 8) PANEL DIRECTERIES 408.4 |
|
09/29/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EM LIGHTING NOT WORKING 2) BOXES MORE THAN 1/4"314.20 3) REVISE PANEL DIRECTORIES 408.4 4) MODULAR FURNITURE TO BE PER 605.5 & 7 5) NEED TO SEE MODULAR FURNITURE CONNECTIONS 6) OK TO BRING FURNITURE ON SITE |