Permit: T11CM02812

Parcel: 123090660


Addresses:

2512 E DRACHMAN ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/14/2011 BUILDING - FINAL Approved IVRS - Inspection :*
1) FINISH ITEMS 2,3 & 5
2) OK AFTER CORRECTIONS
09/13/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAINTAIN WORKING CLEARANCES AT INTERVERTER/DISCONNECT 110.26
2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT TERMINAL MARKED FOR CONDUCTOR
3) GROUNDING ELECTRODE TO BE CONTINOUS 250.64 OR PROVIDE PHYSICAL PROTECTION
4) GROUNDED CONDUCTOR TO BE CORRECTLY MARKED
5) INSTALL WEB LUG PER MANUFACTURES INSTRUCTIONS
2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT TERMINAL MARKED FOR CONDUCTOR
3) GROUNDING ELECTRODE TO BE CONTINOUS 250.64 OR PROVIDE PHYSICAL PROTECTION
4) GROUNDED CONDUCTOR TO BE CORRECTLY MARKED
5) INSTALL WEEB LUG PER MANUFACTURES INSTRUCTIONS
09/12/2011 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
09/09/2011 BUILDING - FINAL Cancelled IVRS - RI canceled