Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) FINISH ITEMS 2,3 & 5 2) OK AFTER CORRECTIONS |
|
| 09/13/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCES AT INTERVERTER/DISCONNECT 110.26 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT TERMINAL MARKED FOR CONDUCTOR 3) GROUNDING ELECTRODE TO BE CONTINOUS 250.64 OR PROVIDE PHYSICAL PROTECTION 4) GROUNDED CONDUCTOR TO BE CORRECTLY MARKED 5) INSTALL WEB LUG PER MANUFACTURES INSTRUCTIONS 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT TERMINAL MARKED FOR CONDUCTOR 3) GROUNDING ELECTRODE TO BE CONTINOUS 250.64 OR PROVIDE PHYSICAL PROTECTION 4) GROUNDED CONDUCTOR TO BE CORRECTLY MARKED 5) INSTALL WEEB LUG PER MANUFACTURES INSTRUCTIONS |
|
| 09/12/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |
|
| 09/09/2011 | BUILDING - FINAL | Cancelled | IVRS - RI canceled |