Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONNECT OUTSIDE AIR DUCT TO A/C UNIT 2) PROVIDE 190 CFM OF FRESH AIR 3) SUPPORT ALL FLEX DUCTS OFF OF CONDUITS AND PIPES |
|
| 08/31/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE INTERLOCK EXHAUST HOOD WITH OVEN 2) GLUE OR TAPE ARAMFLEX JOINTS 3) REMOVE ANY DUCT TAPE USED OUTDOORS 4) NEED TO SEE DRYER VENT BACK DRAFT DAMPERS 5) PROVIDE WASHERS AND WING NUTS ON CLEANOUTS 6) SEAL AROUND DRYER VENTS AT WALL PENETRATION 7) REPAIR GREASE DUCT AT TOP OF FAN CURB AND PROVIDE A GASKET 8) PAINT ALL EXPOSED PVC WITH LATEX 9) PROVIDE AIR BALANCE REPORT 10) TESTED HEAT SENSOR |