Permit: T11CM02785

Parcel: 128100560

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02785

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/22/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONNECT OUTSIDE AIR DUCT TO A/C UNIT
2) PROVIDE 190 CFM OF FRESH AIR
3) SUPPORT ALL FLEX DUCTS OFF OF CONDUITS AND PIPES
08/31/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NEED TO SEE INTERLOCK EXHAUST HOOD WITH OVEN
2) GLUE OR TAPE ARAMFLEX JOINTS
3) REMOVE ANY DUCT TAPE USED OUTDOORS
4) NEED TO SEE DRYER VENT BACK DRAFT DAMPERS
5) PROVIDE WASHERS AND WING NUTS ON CLEANOUTS
6) SEAL AROUND DRYER VENTS AT WALL PENETRATION
7) REPAIR GREASE DUCT AT TOP OF FAN CURB AND PROVIDE A GASKET
8) PAINT ALL EXPOSED PVC WITH LATEX
9) PROVIDE AIR BALANCE REPORT
10) TESTED HEAT SENSOR