Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2012 | ELECTRIC - ABOVE CEILING | Approved | ||
| 11/22/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK RECEPTION AREA 2) METAL ARC SHIELDS NOT APPROVED FOR USE |
|
| 11/16/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) UDV CABLING TO BE 725.8, 800.24 AND 300.11 2) SUPPORT M/C CABLES 334.30 AND 300.11 3) EMT TO BE 300.11 4) BOXES MORE THAN 1/4" 314.20 |
|
| 10/14/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOX OVER FILLED, WILL CHECK AT FINAL |
|
| 10/06/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK BATHROOM WALLS & LIDS |