Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T11CM02683
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2012 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/02/2012 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPLY TO PHARMACY RESTROOM IS MISSING 2) SUPPLY TO PUBLIC RESTROOM IS MISSING 3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 4) E.F./A TO RUN CONTINOUSLY 5) SUPPORT PVC EVERY 4' 6) USE PURPLE PRIMER PRIOR TO GLUING FITTINGS 7) PROVIDE AN OVERFLOW SENSOR 8) EXTEND VENT IN CONDENSATE ABOVE DRAIN PAN 9) DO NOT SUPPORT DRAIN LINE WITH WIRE 10) PROVIDE 1/8" PER FEET SLOPE 11) PROVIDE SCREEN IN ROOF JACK ON ROOF |
|