Permit: T11CM02683

Parcel: 11615082A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02683

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
10/11/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WASTE AND SOIL PIPING WITH TEST FOR SINK & LAV OK, SUBJECT TO APPROVED PLANS
2) REVENTED AT DEMO FS ON SECOND LEVEL
3) DOMESTIC WATER OK TO INSULATE
4) WOULD LIKE TO SEE A WYE INSTALLED FOR TESTING
10/06/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*