Permit: T11CM02674

Parcel: 141316380

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T11CM02674

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2012 BUILDING - FINAL Approved IVRS - Inspection :*
03/14/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CERTS NEEDED
2) MAXIMUM AMPERAGE FOR 14 AWG WIRE OF 15 AMPS
3) LABEL ALL BREAKERS AT PANEL
4) MAX OVERCURRENT PROTECTION MARKED AT AIR HANDLER OF 15 AMPS