Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/21/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/09/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TOP OF HOOD DOES NOT HAVE 18" CLEARANCE 2) OK TO DBL LAYER TOP OF HOOD WITH FIRE WRAP 3) SECURE WITH PINS OR BANDING 4) PROVIDE A HINGE KIT FOR EXHAUST FAN AND GUARD RAILS AT FAN & COOLER IF WITHIN 10' OF EDGE OF ROOF 5) CHECKED 2 LAYERS OF FIRE WRAP-OK TO PROCEED |
|
| 08/26/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST (LEAK) ON 4' DUCT OK |