Permit: T11CM02665

Parcel: 129011370


Addresses:

800 S TUCSON BL 02

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/21/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
09/21/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/09/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TOP OF HOOD DOES NOT HAVE 18" CLEARANCE
2) OK TO DBL LAYER TOP OF HOOD WITH FIRE WRAP
3) SECURE WITH PINS OR BANDING
4) PROVIDE A HINGE KIT FOR EXHAUST FAN AND GUARD RAILS AT FAN & COOLER IF WITHIN 10' OF EDGE OF ROOF
5) CHECKED 2 LAYERS OF FIRE WRAP-OK TO PROCEED
08/26/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SMOKE TEST (LEAK) ON 4' DUCT OK