Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T11CM02662
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2012 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
04/14/2012 | ELECTRIC - PROGRESS | Partial Approval | SOLAR TAP CONNECTIONS IN SWITCH GEAR OK. TAP CONDUCTORS PHYSICALLY SEPARATED AND ROUTED INSIDE CARFLEX. ALL SOLAR CONDUCTORS LABELED AND IDENTIFIED. OK TO RE-ENERGIZE CLEARANCE CALLED IN TO TEP. CHECK # 3170 IN AMOUNT OF $165 RECIEVED FOR THIS SATURDAY INSPECTION. FEES ADDED TO ACTIVITY T11CM02560 (BOTH INSPECTIONS DONE AT SAME TIME) |
|
04/13/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER FROM ENGINEER OF RECORD WITH DIRECTION FOR CUSTOMER SIDE PV AC CONDUCTORS ENTRANCE TO ACCOMADATE LINE SIDE TAP OF SES 2) CONTRACTOR WILL ROUTE PV CONDUCTORS IN CAR FLEX TO ACT AS BARRIER, WILL SUPPORT AS FAR AWAY FROM EXISTING BUSS IN EQUIPMENT AS POSSIBLE-SUPPORT WITH TIE WRAP |
|
04/09/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK CONTINUE ROOF PVC ARRAY-HOME RUNS NOT IN YET FROM COMBINERS TO INVERTERS |