Permit: T11CM02661

Parcel: 13314227C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM02661

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/11/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) IF REUSING EXISTING FAN COILS, DUCTING, VAV'S THE DUCTING AND PIPING WILL HAVE TO BE SUPPORTED
2) FAN COILS WILL NEED SECONDARY DRAIN PANS WITH OVERFLOW SENSORS
3) THERE IS NO RETURN AIR BEING DRAWN FRONM THE PLENIUM CEILING
4) OK TO USE EXISTING FRESH AIR TO PLENIUM UNTIL NEW FRESH AIR UNIT IS INSTALLED