Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM02654

Parcel: 13216600A


Addresses:

4004 S PARK AV 02


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T11CM02654

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2012 ELECTRIC - PROGRESS Approved
10/15/2012 ELECTRIC - PROGRESS Partial Approval PANEL SCHEDULE
LABEL X FOR MORE DISC DESIGNATION
10/09/2012 ELECTRIC - PROGRESS Partial Approval 1. BOND XFORMER TO BLD STEEL
2. BOND BUSHINGS ON FUEX CONNECTION AT 112 KVA
3. PROVIDE ACCESS TO 24X24 J BOX
4. UPDATE PANEL SCHEDUKLE