Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) R-30 FIBERGLASS BAIT CEILING AND R-18 FIBERGLASS BAIT WALLS PER CONTRACTOR |
|
| 01/12/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND WIRES UNDER SAME LUG MUST BE SAME SIZE 2) SECONDARY CONDENSATE LINE NEEDS ELBOW 3) ROOF A/C SHOULD BE ON RED WOOD OR PRESSURE TREATED WOOD 4) ALL EXTERIOR SPOT LIGHTS MUST POINT DOWN-45 DEGREE OR LESS 5) SECONDARY MEANS OF EGRESS ? |