Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM02638
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/15/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/17/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PAPERWORK FOR UNIT TO BE LISTED, STATES MARKINGS TO BE ON EXTERIOR OF UNIT-LIGHT NOT WORKING |
|
10/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY LISTING OF EQUIPMENT 2) NEED SUPPORT WIRES ON CANS 3) SUPPORT VDV CABLING 760.24 4) EM LIGHTS TO BE PER 700.12 (F) 5) MISSING LIGHTS 6) WHERE IS DISCONNECTING MEANS FOR CHILLER |
|
09/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONTROL WALL |
|
09/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS MRI ROOM 2) OK FEEDER ABOVE CEILING HALLWAY |
|
09/19/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WALL COVERED WITHOUT INSPECTION-NEED TO OPEN TO INSPECT |