Permit: T11CM02637

Parcel: 10605096B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/09/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/08/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS AT PANEL B
2) SUPPORT CONDUITS AT PANEL B
3) FILL UNUSED OPENINGS IN PANEL
4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
5) WORKING CLEARANCES FOR PANEL A WERE NOT CODE COMPLIANT AT TIME OF INSTALL-EXISTING PANEL
09/01/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/31/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EXTERIOR LIGHT TO BE SUPPORTED WITH SISMEC WIRE, ALSO SUPPORT CONDUITS AT DEMISING WALL CEILING AND TO RIGHT OF DOOR (WINDOWS)