Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/08/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE FITTINGS AT PANEL B 2) SUPPORT CONDUITS AT PANEL B 3) FILL UNUSED OPENINGS IN PANEL 4) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 5) WORKING CLEARANCES FOR PANEL A WERE NOT CODE COMPLIANT AT TIME OF INSTALL-EXISTING PANEL |
|
| 09/01/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/31/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) EXTERIOR LIGHT TO BE SUPPORTED WITH SISMEC WIRE, ALSO SUPPORT CONDUITS AT DEMISING WALL CEILING AND TO RIGHT OF DOOR (WINDOWS) |