Permit: T11CM02615

Parcel: 12620001C


Addresses:

1100 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T11CM02615

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2012 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
02/10/2012 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1)
2) SERVICE CONDUCTORS TO ENTER SECTION SERVED 408.3 CANNOT PASS UNPROTECTED CONDUCTOR 230.7
3) SERVICE NIPPLE 400 AMP TO CT OVER FILLED BY CALCULATIONS
4) PARALELL CONDUCTOR SES TO 400 AMP DISCONNECT NEUTRAL OR GROUNDED CIRCUIT CONDUCTORS TO BE PARALELL OR SIZED PER 250.24 (C) 1 & 2 AND 250.66
5) OK UNDERGROUND AS MARKED ON PLANS