Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T11CM02615
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2012 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
02/10/2012 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) 2) SERVICE CONDUCTORS TO ENTER SECTION SERVED 408.3 CANNOT PASS UNPROTECTED CONDUCTOR 230.7 3) SERVICE NIPPLE 400 AMP TO CT OVER FILLED BY CALCULATIONS 4) PARALELL CONDUCTOR SES TO 400 AMP DISCONNECT NEUTRAL OR GROUNDED CIRCUIT CONDUCTORS TO BE PARALELL OR SIZED PER 250.24 (C) 1 & 2 AND 250.66 5) OK UNDERGROUND AS MARKED ON PLANS |