Permit: T11CM02614

Parcel: 138150830


Addresses:

6751 S 5TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02614

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) ITEMS 3 THRU 9 ARE N/A, AS THESE ARE OF AN EXISTING CONDITION AND NOT WITHIN THE SCOPE OF WORK
09/06/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) T-STAT WIRE AT EXTERIOR IS TO BE PROTECTED FROM DAMAGE BY CONDUIT OR OTHER APPROVED MEANS
2) LINE SET PIPE INSULATION AT EXTERIOR IS TO BE U.V. PROTECTED BY AN APPROVED MEANS
3) ALL PVC PIPE AND FITTINGS ARE TO HAVE PRIMER AND PRIMER IS TO BE PURPLE IN COLOR PER U.P.C.
4) PROVIDE SECONDARY DRAIN
5) LINE SET INDOORS NOT PROPERLY INSULATED AND PROVIDE LISTED MATERIALS
6) PROVIDE APPROVED CONNECTOR WHERE CONTROL WIRING ENTERS CABINET
7) CONDUIT AT DISCONNECT BROKEN
8) INDOW UNIT UNDER FUSED
9) PROVIDE P-TRAP AT INDOOR COIL
09/01/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*