Permit: T11CM02593

Parcel: 136070630


Addresses:

1503 S AIDA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/04/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/29/2011 ELECTRIC - FINAL Denied IBC/IRC 106.4 WORK HAS NOT BEEN INSTALLED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS.

1) NEC 690.64 -60 AMP SOLAR BREAKER IN PANEL OVERSIZED
2) NEC 690.17 - LABEL MISSING ON DISCONNECT
3) NEC 690.43 -GROUNDING BONDING MISSING ON SPLICING RAILS