Permit: T11CM02560

Parcel: 13216600A


Addresses:

4004 S PARK AV 01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM02560

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/07/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FIX BROKEN FEEDER BY INVERTER #1
2) INSTALL SIGNAGE PER 690
3) GEC TO GROUND ROD
4) BUSHINGS ON CONDUIT TERM'S IN INVERTERS (PVC)
04/14/2012 ELECTRIC - INTERMEDIATE Partial Approval SOLAR TAP CONNECTIONS IN SWITCH GEAR OK. TAP CONDUCTORS PHYSICALLY SEPARATED AND ROUTED INSIDE CARFLEX. ALL SOLAR CONDUCTORS LABELED AND IDENTIFIED.

OK TO RE-ENERGIZE CLEARANCE CALLED IN TO TEP.
CHECK # 3170 IN AMOUNT OF $165 RECIEVED FOR THIS SATURDAY INSPECTION.
04/13/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER FROM ENGINEER OF RECORD WITH DIRECTION FOR ENTRANCE OF PVC AC CONDUCTORS THRU CUSTOMER LOAD SIDE OF SES TO ACCOMADATE LINE SIDE TAP INTO BUSS
04/10/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REVIEW TIE IN FOR OFF HOURS POWER KILL-NEED TO DISCUSS WITH LEE RAY PRIOR TO SAT. 4/14/12
03/20/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCUSSED POSSIBLE BUSS OPTIONS FOR PV TIE IN
2) OK PER INSPECTOR TO TERMINATE CONDUIT WITH PV SUPPLY TO LOAD SIDE, CONDUCTORS WILL PASS THRU OPEN WINDOW BETWEEN LOAD COMPARTMENT TO BUSS LINE SIDE, WILL TIE INTO LUGS ON MAIN BRKR LINE TAP-CONTRACTOR WILL CHANGE OUT EXISTING LUGS TO STACKED TYPE LUGS TO ALLOW PV TIE IN WITHOUT MODIFIACTIONS TO BUSS. IT MAYBE NECESSARY TO SLEEVE CONDUCTORS WITH CAR FLEX TO PROVIDE ISOLATION THRU LOAD COMPARTMENT, WILL DISCUSS WITH RAY M.