Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2011 | ELECTRIC - FINAL | Denied | IBC/IRC 106.4 WORK HAS NOT BEEN INSTALLED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. 1) RAIL SPLICES TO BE BONDED & WIRES TO PANELS TO BE IN RACEWAY ON ROOF 2) NEC 230.17 -MAIN DISCONNECT MISSING IN PANEL 3) 1/2' KO SEAL MISSING ON RIGHT SIDE OF PANEL |