Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/13/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) INSULATE DUCT ABOVE CEILING 2) INSULATE LINE SETS IN RETURN PLENIUM 3) PROVIDE SECONDARY DRAIN AT COIL 4) PROVIDE PROPER FALL AT P-TRAP 5) SEAL ALL DUCT JOINTS 6) BATHROOM EXHAUST NOT CONNECTED |
|
| 09/12/2011 | MECHANICAL - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR CHARLES GATES #661-1612 |