Permit: T11CM02537

Parcel: 120052730

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM02537

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) STRAP M/C CABLE PER CODE 12" + 6'
2) LOOSE FITTINGS ON CONDUIT
3) PLANS CALL FOR 125 BREAKER TO FEED PANEL "B" FEEDER WIRE SIZE PER 310.15 NEC
4) PANEL "B" LOOSE
09/23/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WALLS CEILING COVERED PRIOR TO INSPECTION. OPEN WALLS AT NEW PANEL & OPEN CEILING TILES AROUND NEW WORK ABOVE CEILING (WALLS) WHERE NEW CORCUITS ADDED FOR POWER, BACK TO PANELS