Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/03/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH ITEMS 1 & 5 PREVIOUS INSPECTION |
|
| 09/30/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT M/C CABLES PER 330.30 AND 300.11 2) BOXES OVER FILLED 3) SUPPORT WIRE NEEDED FOR EXIT SIGNS 4) SECURELY ATTACH FIXTURES TO GRID 410.16 5) REVISE PANEL DIRECTORY 408.4 6) FILL UNUSED OPENING JUNCTION BOX 7) SUPPORT CONDUITS SIDE PANEL 3' 8) EM LIGHTS TO BE PER 700.12 (F) 9) BOXES MORE THAN 1/4" 314.20 |
|
| 08/26/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |