Permit: T11CM02526

Parcel: 10603170E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/04/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/03/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH ITEMS 1 & 5 PREVIOUS INSPECTION
09/30/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT M/C CABLES PER 330.30 AND 300.11
2) BOXES OVER FILLED
3) SUPPORT WIRE NEEDED FOR EXIT SIGNS
4) SECURELY ATTACH FIXTURES TO GRID 410.16
5) REVISE PANEL DIRECTORY 408.4
6) FILL UNUSED OPENING JUNCTION BOX
7) SUPPORT CONDUITS SIDE PANEL 3'
8) EM LIGHTS TO BE PER 700.12 (F)
9) BOXES MORE THAN 1/4" 314.20
08/26/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*