Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM02502
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/18/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/23/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED ARC SHIELDS, METAL NOT APPROVED 2) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 200.7 3) BOXES MORE THAN 1/4" 314.20 4) PROPERLY GROUND BOXES AND DEVICES 5) FINISH VDV 6) NEED COVER PLATE FOR RECEPT ABOVE CEILING |