Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM02502

Parcel: 10321341A


Addresses:

2140 W GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM02502

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH #1 & 2 PREVIOUS INSPECTION-CHECK ON FINAL
12/08/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) M/C CABLE IF SUPPORTED TO BE PER 300.11
2) VDV CABLIONG TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11
3) SWITCH WIRING TO BE PER 517.13
4) SECURE 2 X 4 FIXTURES TO GRID 410.16
5) MISSING RECEPT SCREWS ON INDUSTRIAL COVER 406
10/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PATIENT CARE WALLS
10/21/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL WIRING IN AREA TO BE 517.13
2) FILL ALL UNUSED OPENINGS-NOT OLD FITTINGS
3) TIGHTEN LOOSE FITTINGS
10/19/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*.
1) MEET WITH CONTRACTOR TO DISCUSS PATIENT CARE AREA
2) PLAN REVIEWED IN ERROR
10/18/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONSULT ROOM IS A PATIENT CARE AREA AND WIRING TO BE PER 517
2) M/C CABLE IN WALLS DOES NOT MEET REQUIREMENT
10/13/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AS MARKED
10/12/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SECURE M/C ON HORIZONTALS
2) PROTECT M/C AT TOP PLATE
3) FINISH VDV IN WALLS NOTE: 725.8 AND 800.24