Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM02502
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH #1 & 2 PREVIOUS INSPECTION-CHECK ON FINAL |
|
| 12/08/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) M/C CABLE IF SUPPORTED TO BE PER 300.11 2) VDV CABLIONG TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11 3) SWITCH WIRING TO BE PER 517.13 4) SECURE 2 X 4 FIXTURES TO GRID 410.16 5) MISSING RECEPT SCREWS ON INDUSTRIAL COVER 406 |
|
| 10/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PATIENT CARE WALLS |
|
| 10/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ALL WIRING IN AREA TO BE 517.13 2) FILL ALL UNUSED OPENINGS-NOT OLD FITTINGS 3) TIGHTEN LOOSE FITTINGS |
|
| 10/19/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*. 1) MEET WITH CONTRACTOR TO DISCUSS PATIENT CARE AREA 2) PLAN REVIEWED IN ERROR |
|
| 10/18/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONSULT ROOM IS A PATIENT CARE AREA AND WIRING TO BE PER 517 2) M/C CABLE IN WALLS DOES NOT MEET REQUIREMENT |
|
| 10/13/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AS MARKED |
|
| 10/12/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SECURE M/C ON HORIZONTALS 2) PROTECT M/C AT TOP PLATE 3) FINISH VDV IN WALLS NOTE: 725.8 AND 800.24 |