Permit: T11CM02501

Parcel: 136127600


Addresses:

3573 S BURNETT PL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/25/2012 FRAMING Approved IVRS - Inspection :*
04/20/2012 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CALL FOR WHEN ALL INTERMEDIATES ARE COMPLETE
03/30/2012 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUBMIT DETAL FOR RIDGE BEAM PER PREVIOUS INSPECTION
2) DBL UP STUDS AT HOLD DOWNS AND NAIL WITH 16 D NAILS
3) SIZE PLAN REVISION NEEDED FOR MFG RAFTERS TO 2 X
4) SUBMIT DETAIL FOR HINGED EAST WALL
5) APPROVED FASTENERS NEEDED IN STRAPS AND JOIST HANGERS
03/28/2012 FRAMING Not ready for Inspection IVRS - Inspection :*
1) FRAMING DONE WITH INTERMEDIATES
2) STRAP GARAGE GLUE LAMB POST BEAM HEADERS
3) INSTALL ALL T-111 SIDING PRIOR TO 1025 INSPECTION
4) DBL STUB ALL HOLDOWNS
5) NOTE 1 FROM PREVIOUS
6) SUBMIT DETAIL FOR RIDGE BEAM INSTALLATION AT EXISTING
7) NO DETAIL BALLOON FRAMING FAMILY ROOM EAST WALL
8) STOPPED INSPECTION
03/15/2012 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 2 X 8 BOX HEADERS OR EQUIVALANT NEEDED AT BACK WINDOW FOR FAMILY ROOM (4 X 6 INSTRALLED ON THEIR SIDE)
2) INSTALL 1/2" COX PLYWOOD AT EXTERIOR PER PLAN
3) ANCHOR BOLTS NEEDED IN BOTTOM PLATE WITHIN 12" OF SEAMS
4) EXPOSE BEARING OF BEAM AT EXISTING EXTERIOR WALL FOR RIDGE BEAM