Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM02472

Parcel: 120084090


Addresses:

155 W TENNESSEE ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
05/25/2012 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
05/22/2012 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE RATE OVERHANG 2ND UNIT WITHIN 36" PROPERTY LINE
2) REAR PORCH 2 X 4 RAFTERS NOT 16" PER PLAN 4 X 6 HEADER OVER SPANNED
3) KEY NOTE X CALLS FOR 2 X 8/2 X6 INSTALLED. WHAT IS METHOD OF ATTACHMENT ? SUBMIT DETAIL
4) EXPOSE ALL FOOTERS TO VERIFY DEPTH PER PLAN
5) PROVIDE LETTER HEAD FROM LICENSED ELECTRICIAN AND PLUMBER STATING ALLL WORK TO CODE FOR SAFETY OR EXPOSE ALL FOR INSPECTION
6) 110 SERVICE OUTLET ROOF TOP UNIT. CONDENSATE LINE TERMINATE ROOFS EDGE