| 11/23/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/07/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE ROOF LOAD CALCS, UNIT IS SUPPORTED BY ONE 2 X 6 RAFTER (CUT AND STACK) 2) PROVIDE ISOMETRIC GAS PIPING DIAGRAM 3) SERVICE OUTLET NOT PROPERLY WIRED |