Permit: T11CM02441

Parcel: 131081460


Addresses:

5942 E 27TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/14/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/09/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TAPE ENDS OF WHITE WIRES FOR A/C UNIT WITH BLACK TAPE
2) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
3) VENT ON CONDENSATE DRAIN MUST BE DOWN STREAM OF THE TRAP
4) PAINT ALL EXPOSED PVC WITH LATEX PAINT
5) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND
6) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
7) SECTURE THE ANGLE NON STAND TO THE ROOF
8) PROVIDE THE HOOD OVER THE FURNACE EXHAUST PORT ON SIDE OF UNIT
9) PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW UNIT ON THE ROOF