Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/08/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/06/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAIN BREAKER 200 SOLAR BREAKER PLANS CALL FOR 40 NOT 50 2) GEC TO BE BONDED ON BOTH ENDS WHEN USING METAL PIPE 3) RACEWAYS TO BE 1" NOT 3/4 4) COMBINER HAS 20 AMP BREAKER PRINT CALLS FOR 15 AMPS 5) PLEASE BE THERE FOR NEXT INSPECTION |