Permit: T11CM02420

Parcel: 141312790

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T11CM02420

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2011 BUILDING - FINAL Approved IVRS - Inspection :*
10/25/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAIN BREAKER TO BE 175A
2) 60A BREAKER TO BE LABELED
3) GEC TO BE BONDED ON BOTH ENDS
4) BREAKERS IN COMBINER MISSING LABELS
5) #8 MISSING FROM COMBINER TO ROOF TO BOND MIRCO INVERTERS
6) CANNOT USE SUB PANEL FOR SOLAR RACEWAY 404.3 B