Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM02420
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAIN BREAKER TO BE 175A 2) 60A BREAKER TO BE LABELED 3) GEC TO BE BONDED ON BOTH ENDS 4) BREAKERS IN COMBINER MISSING LABELS 5) #8 MISSING FROM COMBINER TO ROOF TO BOND MIRCO INVERTERS 6) CANNOT USE SUB PANEL FOR SOLAR RACEWAY 404.3 B |