Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/27/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE A MEANS OF SECONDARY DRAIN ON INDOOR COILS 2) PROVIDE DUCT SMOKE DETECTORS AT ALL UNITS OVER 2000 CFM 3) CONDENSATE CANNOT BE REDUCED AT ANY TIME (LAV TAIL PIECE) |