| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK AND CLAMP GAS LINE & CONDENSATE DRAIN 2) PAINT PVC WITH LATEX PAINT 3) SECURE ELECTRIC CONDUIT 4) UNIT OVERFUSED |