Permit: T11CM02373

Parcel: 131100870


Addresses:

5518 E 24TH ST

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
04/25/2012 BUILDING - PROGRESS Approved
01/11/2012 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER PROOF COVER NEEDED FOR EXTERIOR OUTLETS
2) CHANGE BREAKERS OUT TO MATCH PANEL MANUFACTURE
3) EXTEND PRV TO WITHIN 6" OF GROUND FOR WATER HEATER AT EXTERIOR
4) MAXIMUM OVERCURRENT PROTECTION FOR WATER HEATER OF 25 AMP
5) BLANK SPACER NEEDED FOR UNUSED KNOCKOUT AT DEAD FRONT OF PANEL