Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2012 | BUILDING - PROGRESS | Approved | ||
| 01/11/2012 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER PROOF COVER NEEDED FOR EXTERIOR OUTLETS 2) CHANGE BREAKERS OUT TO MATCH PANEL MANUFACTURE 3) EXTEND PRV TO WITHIN 6" OF GROUND FOR WATER HEATER AT EXTERIOR 4) MAXIMUM OVERCURRENT PROTECTION FOR WATER HEATER OF 25 AMP 5) BLANK SPACER NEEDED FOR UNUSED KNOCKOUT AT DEAD FRONT OF PANEL |