Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM02370
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/27/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEUTRAL (WHITE) CONDUCTORS TO BREAKER AT PANEL AND DISCONNECTS 2) OVERSIZED BREAKER FOR A/C COMPRESSOR 3) MARK OVER CURRENT MAXIMUM AT UNIT |