Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T11CM02367
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2011 | MECHANICAL - INTERMEDIATE | Approved | 1) SHOW DOCUMENTATION THAT THE FACTORY CONDENSATE PUMP WILL ACTUALLY PUMP THE WATER THRU A 4' TO 5' VERTICLE 3/8" DIAMETER DRAIN LINE 2) PROVIDE A HOSE CLAMPN AT CONNECTION TO BRASS FITTING 3) FINISH CONNECTING FIRE/SMOKE DAMPERS TO FIRE ALARM 4) WILL THE OVER FLOW SENSOR ON PUMP BE HOOKED UP ? 5) WILL CHECK CORRECTIONS ON FINAL |
|
09/12/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RELOCATE CONDUIT BLOCKING ACCESS TO VAV 2) OK TO INSULATE CONDENSATE DRAIN 3) STILL NEED TO SEE FINAL CONNECTIONS TO I.T. ROOM |