Permit: T11CM02365

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM02365

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/12/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND SOFFIT CANS MALL, BACK ROOMS, BATHROOM AND STOCK ROOM
09/06/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT M/C CABLE AT SHALLOW STUDS 330.17
2) VERIFY BOX FILL 314.16
3) PLEASE PROVIDE LETTER FROM ENGINEER FOR USE OF M/C CABLE
4) PROTECT ENDS OF VDV RACEWAYS FROM SHARP METAL EDGES
5) OK WALLS SUBJECT TO LETTER AND CORRECTIONS-SALES FLOOR