Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM02353
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE 2) OVER CURRENT FOR AIR HANDLER 15 AMP MAXIMUM |
|
09/07/2011 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE BEADED COLLARS ON ALL CEILING DIFFUSERS 2) SUPPORT DIFFUSERS 3) PROVIDE AN OVERFLOW SENSOR 4) SLOPE CONDENSATE DRAIN MINIMUM 1/8" PER FT. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 5) MARK FAN COIL DATA PLATE WITH PROPER HEAT STRIP AND FUSE DISCONNECT ACCORDINGLY 6) PROVIDE ISOLATORS AS PER PLANS 7) TERMINATE CONDENSATE PER PLANS, SUPPORT EVERY 4' AND INSULATE PER PLANS 8) FOR FINAL BE SURE TO PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX ON ROOF 9) BALANCE O.S.A. PER QUANTITIES ON PLANS, ALSO SUPPLY DIFFUSERS |