Permit: T11CM02353

Parcel: 136261260

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM02353

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) OVER CURRENT FOR AIR HANDLER 15 AMP MAXIMUM
09/07/2011 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE BEADED COLLARS ON ALL CEILING DIFFUSERS
2) SUPPORT DIFFUSERS
3) PROVIDE AN OVERFLOW SENSOR
4) SLOPE CONDENSATE DRAIN MINIMUM 1/8" PER FT. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
5) MARK FAN COIL DATA PLATE WITH PROPER HEAT STRIP AND FUSE DISCONNECT ACCORDINGLY
6) PROVIDE ISOLATORS AS PER PLANS
7) TERMINATE CONDENSATE PER PLANS, SUPPORT EVERY 4' AND INSULATE PER PLANS
8) FOR FINAL BE SURE TO PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX ON ROOF
9) BALANCE O.S.A. PER QUANTITIES ON PLANS, ALSO SUPPLY DIFFUSERS